基于CAESARⅡ的高层建筑空调管道应力的温度影响分析 被引量:1

Study of Influence of Pipe Temperature on Stress of Air-Conditioning Pipe in High-rise Building Based on CAESARⅡ
下载PDF
导出
摘要 基于管道应力软件CAESARⅡ对空调管道在不同温度区间的操作应力和二次应力进行分析,得出结论:管道温度在低温区间内,管道操作应力随温度的升高而减小但变化幅度极小。在高温区间内,管道操作应力随温度的升高而增大且变化幅度较大。而管道的二次应力在整个温度区间内都随着温度的升高而增加,并且高温对其影响更大。 Based on the pipeline stress software CAESARⅡ,the operating stress and secondary stress of air conditioning pipes with different temperatures are analyzed under a certain pressure condition. The result shows that∶the operating stress of the pipeline decreases slightly at low temperature and increases evidently at high temperature with the increasement of the pipe temperature. While the secondary stress of air conditioning pipes increases with the increasement of the pipe temperature at whole temperature interval, especially at high temperature.
作者 黄正凯 邓亚宏 肖阳 聂伟 杨仲卿 孟胜利 Huang Zhengkai;DengYahong;Xiao Yang;Nie Wei;Yang Zhongqing;Meng Shengli(The Second Construction of China Construction Third Engineering Bureau,Wuhan,Hubei 430070;College of Power Engineering,Chongqing University,Shapingba,Chongqing 400000;Central China Electric Power Engineering Corporation Limited,Zhengzhou,Henan 450000)
出处 《江西建材》 2018年第12期16-18,共3页 Jiangxi Building Materials
关键词 空调管道 应力分析 温度 CAESARⅡ Air conditioning pipe Stress analysis Temperature CAESARⅡ