摘要 研究结合了500kV官山变电站直流融冰兼SVC装置油浸式空心电抗器的故障情况,分析了故障产生的原因,提出新的整改方案,并通过ANSYS电磁仿真软件,对新方案进行仿真分析。仿真结果表明,该方案有效地解决了油浸式空心电抗器结构不稳定的缺陷,提高了油浸式电抗器的可靠性。 The research combined with the oil-immersed hollow reactor failure of the DC ice-melting device and SVC in 500 kV Guanshan transformer substation,analyzes the causes of failure,puts forward and introduces in detail the feasible improvement scheme,and through ANSYS electromagnetic simulation software,simulates the new scheme.The simulation results show that the scheme effectively solves the defect of the unstable structure of oil-immersed hollow reactor and improves the reliability of oil-immersed reactor.
出处 《电力学报》 2018年第4期322-331,共10页 Journal of Electric Power
关键词 变电站 电抗器 仿真 ANSYS transformer substation reactor simulation ANSYS