摘要
独立式电流互感器应用于敞开变电站中,其一次绕组串接在线路中,稳定可靠的电流互感器能够准确的反映一次线路的状况,对系统的可靠运行有着不可替代的作用,本文通过一起500kV电流互感器二次电流三相不平衡的故障分析,判断是一次电流存在分流现象,通过试验验证及解体分析,证明了判断的正确性,同时根据故障情况,提出相应解决方案,有效地解决了电流互感器二次电流不平衡的问题。
Independent type current transformer is applied to open the transformer substation,the concatenated primary winding in the circuit,stable and reliable current transformer can accurately reflect the status of a line,hasan irreplaceable role for the reliable operation of the system,based on the 500 kv current transformer with secondary current of three-phase unbalanced fault analysis,judgment is a current shunt phenomenon,through testand analysis of collapse,proved the correctness of the judgment,at the same time according to the fault condition,put forward the corresponding solutions,effectively solve the current transformer secondary current imbalances.
作者
张超军
贺永明
赵建磊
王红庆
ZHANG Chao-jun;HE Yong-ming;ZHAO Jian-lei;WANG Hong-qing(Pinggao Group Co.,Ltd.,Pingdingshan Henan 467001,China)
出处
《装备制造技术》
2018年第9期247-249,258,共4页
Equipment Manufacturing Technology
关键词
变比
准确级
比差
variable ratio
accurate grade difference