期刊文献+

严寒地区超低能耗建筑与节能65%建筑能耗模拟对比分析 被引量:2

The Energy Consumption Analysis of a Super Energy Saving Building in Severe Cold Zone Comparing with the Building with 65% Energy Saving Efficiency
下载PDF
导出
摘要 为进一步提高严寒地区建筑节能潜力,对吉林省某超低能耗建筑进行能耗分析.该超低能耗建筑集毛细管辐射供暖/供冷系统,地源热泵系统,全热回收新风系统,太阳能光热系统等多项节能技术.利用eQUEST软件模拟分析超低能耗建筑能耗,与DB 22/T450-2007《吉林省《居住建筑节能设计标准(节能65%)》参照建筑进行对比分析,全年总能耗节能72.7%,尤其是采暖能耗能节能96.7%,结果表明严寒地区超低能耗建筑节能效果显著. In order to further improve toe energy saving potentiao ofbuioding in severe cood zoneo a super energy saving building in Jilin province is elected to research on energy consumption analysis. This super energy saving building integrates various energy efficiency technologies, including the capillary radiation heating/cooling system, ground-source heat pump system, fresh-air total heat recovery system and solar heating system. The energy consumption of the super energy saving building is simulated and analyzed byeQUESTsoowareoacoordingtotoeDesignStandardforEnergyEfociencyofResidentialBuiodings (Energy Efficiency 65%) in Jilin Province (DB22/T450-2007), the super energy saving building will save 72.7% energy the whole year ,especially the energy consumption of heating can be saved by 96.7% comparing with the same type of energy efficiency 65% building. This proves that the energy efficiency of super energy saving building in severe cold zone is remarkable.
作者 王杨洋 崔正旭 陶进 WANG Yang-yang, CUI Zheng-xu, TAO Jin(Municipal and Environmental Engineering Insitute, Changchun 13 0114,China)
出处 《工程建设与设计》 2018年第21期20-21,24,共3页 Construction & Design for Engineering
基金 住建部2015年低能耗建筑示范工程(2015S1B-002) 吉林省重点科技攻关项目(20170204023SF)严寒地区超低能耗建筑的研究与示范
关键词 严寒地区 超低能耗建筑 能耗分析 节能 severe coldzone super energy savingbuilding energyconsumption analysis
  • 相关文献

同被引文献9

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部