期刊文献+

脱硝供氨蒸发器运行问题分析及处理 被引量:1

Analysis and Treatment of Abnormal Operation of Denitrification Ammonia Evaporator
下载PDF
导出
摘要 中电神头发电有限责任公司2×600 MW机组脱硝液氨蒸发系统,蒸发器热效率差且蒸发器进氨调节阀频繁发生堵塞。通过水侧检查分析,及时改变更了换热水源,经对堵塞物的理化性分析,并咨询有类似情况的其他电厂,查找液氨堵塞的原因,对蒸发器采取物理清洗措施,有效解决了液氨运行过程中的异常问题,保证了脱硝系统安全稳定运行。 The evaporator efficiency of the denitrification liquid ammonia evaporation system of a 2 ×600 MW unit was low and blockagefrequently occurred on the ammonia injection control valve. Through analysis of water side examination, it is found that the water source for heatexchange was changed due to technical modification, and through physical and chemical analysis on the blockage, the blocking reasons were found outand the evaporator was cleaned up, which effectively solved the abnormal problems in the operation process of the liquid ammonia, and ensured thesafe and stable operation of the denitrification system.
作者 徐建成 刘海玲 雷波 XU Jiancheng;LIU Hailing;LEI Bo(Zhongdian Shentou Power Generation Co.,Ltd.,Shuozhou,Shanxi 036011,China)
出处 《山西电力》 2018年第5期59-64,共6页 Shanxi Electric Power
关键词 选择性催化还原系统 液氨 蒸发器 SCR system liquid ammonia evaporator