摘要
在2种不同室外温度工况下,实验研究了系统在开启蓄能除霜模式时的运行特性,分析了蓄热器的放热特性和高、低温级运行特性。结果表明:2种工况下,机组除霜时低温级的吸气压力均在0.236MPa以上,系统除霜性能稳定,高温级的平均制热量能达到正常制热时的55.4%以上,说明蓄热器能够提供稳定的热源。
Experimentally studies the characteristics of energy storage defrosting mode under two outdoor temperature conditions. Analyses the discharge performance of the thermal accumulator and the characteristics of the high and low temperature cycles. The results show that under the two conditions, the suction pressure of the low temperature cycle is higher than 0. 236 MPa. The system defrosting performance is stable. The average heating capacity of the high temperature cycle is more than 55.4% of the normal heating capacity. The thermal accumulator can provide a stable heat source.
作者
曲明璐
唐雍博
秦瑞丰
余倩
彭博
Ou Minglu;Tang Yangbo;Oin Ruifeng;Yu Qian;Peng Bo(University of Shanghai for Science and Technology,Shanghai,China)
出处
《暖通空调》
2018年第11期99-102,共4页
Heating Ventilating & Air Conditioning
基金
国家自然科学基金青年基金资助项目(编号:51406119)
上海市青年科技英才扬帆计划项目(编号:14YF1410000)
关键词
空气源热泵
复叠式循环
蓄热器
除霜
室外温度
低温级
高温级
air-source heat pump
cascade cycle
thermal accumulator
defrosting
outdoor temperature
low temperature cycle
high temperature cycle