期刊文献+

750 kV GIS设备振荡型冲击耐压试验及仿真研究 被引量:7

Oscillatory Impulse Test and Simulation for 750 kV GIS Equipment
下载PDF
导出
摘要 现场冲击耐压试验对于保障GIS设备的安全稳定运行意义重大。在现场通常采用振荡型冲击电压来考核GIS设备的绝缘性能,依托某750 kV变电站,利用数值仿真软件ATP-EMTP对800 kV超高压GIS设备在振荡型雷电冲击波作用下的电压波形和冲击电压发生器参数进行了仿真计算,结合仿真计算结果,在现场对800 kV GIS设备的某一间隔进行了冲击耐压试验以检验设备的绝缘性能,分别进行了50%正负极性额定电压(±840 kV)下的冲击试验,75%正负极性额定电压(±1 260 kV)下的冲击试验,100%正负极性额定电压(±1 680 kV)下的冲击试验,并根据波形要求进行调波。结果表明,仿真计算对现场试验具有重要的指导作用,在现场按照仿真计算得到的冲击电压发生器参数进行设定所得到的试验波形与仿真波形一致。在50%、75%、100%电压作用下设备未发现放电、击穿等现象,设备绝缘性能良好。 In the field, the oscillatory surge voltage is usually used to evaluate the insulatmn perlormance ot t,I3 equipment. Based on a 750 kV substation, the voltage waveform of a 800 kV UHV GIS equipment under oscillatory lightning shock wave and the parameters of surge voltage generator were calculated by the numerical simulation soft- ware ATP-EMTP. According to on the simulation results, on-site impulse withstand voltage test was carried out on a certain interval of the 800 kV GIS equipment to evaluate the insulation performance of the equipment. Impulse tests under 50%, 75%, and 100% of the rated voltage of positive and negative polarities (corresponding to ±840,± 1 260 and ± 1 680 kV) were conducted, respectively, and the waveforms were adjusted according to the requirements. The results show that the simulating calculation plays an important guiding role in the field test. The waveforms of the on- site withstand test with the calculated parameters of surge voltage generator are in accordance with the simulation waveforms. Under the action of 50%, 75% or 100% rated voltage, no discharge or breakdown happened in the equip- ment, and the insulation performance of the equipment is good.
作者 吴旭涛 李秀广 何聪 马波 倪辉 李军浩 WU Xutao;LI Xiuguang;HE Cong;MA Bo;NI Hui;LI Junhao(State Grid Ningxia Electric Power Co.,Ltd.Electric Power Research Institute,Yinchuan 750001,China;School of Electrical Engineering,Xi'an Jiaotong University,Xi'an 710049,China)
出处 《高压电器》 CAS CSCD 北大核心 2018年第11期136-140,共5页 High Voltage Apparatus
关键词 超高压 GIS 振荡冲击电压 现场耐压试验 EHV GIS oscillatory surge voltage on-site withstand voltage test
  • 相关文献

参考文献11

二级参考文献108

共引文献159

同被引文献117

引证文献7

二级引证文献8

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部