摘要
根据一起并联电容器组电容量试验数据异常的分析、处理,建立动态电容器组架构模型,从理论上分析了试验中因测量方法差异导致的人为误差,从而揭示其潜在危害.建议在交接与例行试验时要仔细检查电容器组的接线方式,采用正确的测量方法测量总电容值;在验收交接试验报告时要注意核对交接试验数据与电容器组接线方式的对应.
According to the analysis and treatment of abnormal data of capacitance test of shunt capacitor bank, a dynamic capacitor bank structure model is established. This paper theoretically analyzes the artificial error caused by the difference of measurement method, and it reveals its potential harm. It also suggests that special attention should be paid to the consistency of the measuring connection mode and the operation wiring mode when measuring the capacitor.