摘要
针对中央空调冷却水系统实际运行中出现冷却塔水盘溢水问题,通过对设备运行参数分析,计算冷却水系统运行时候水盘不溢水所需要的水头,以理论数据为依据,改进冷却水管路系统,增加进出水点的落差,解决了水盘溢水问题,保证冷却水系统正常运行。
Aiming at the problems of cooling tower water tray overflow in the actual operation of central ail conditioning cooling water system ,the paper calculates the faucet needed during cooling water system oper-ation without water tray overflow by equipment operating parameters analysis .Based on theoretical data , the cooling water pipeline system has been improved .The gap between points of water in and out is in-creased .The problems of water tray overflow have been solved ,and the normal operation of cooling water system has been ensured .
出处
《长春工程学院学报(自然科学版)》
2014年第3期65-67,共3页
Journal of Changchun Institute of Technology:Natural Sciences Edition
基金
吉林省教育厅"十二五"科学技术项目(2014311)
关键词
溢水
冷却水系统
水头
overflow
cooling water system
faucet