期刊文献+

大型山地风电场电网谐振抑制策略的应用分析 被引量:1

Application and Analysis of Grid Resonance Suppression Strategy of Wind Turbines in Large-scale Mountain Wind Field
下载PDF
导出
摘要 为进一步提高大型山地风电场风电机组的电网系统谐振的适应能力,在建立风电场多机组电网系统阻抗和LCL滤波器的数学模型的基础上,文章详细研究了大型山地风电场的电网谐振及其抑制策略。因为风电场机组数量的增加会改变机组电网系统阻抗,利用准确的数学模型计算出机组谐振频率,再采用有源阻尼的控制策略设计控制器,有效地解决了机组电网谐振问题。通过对大型山地风电场的MATlab仿真和实际应用,验证了电网谐振抑制策略的有效性和优点。 In order to further improve the adaptability of grid system resonance of wind turbines in large-scale mountain wind farm,grid system impedance of wind turbine and mathematical model of LCL filter was established.In this paper,the power grid resonance of large mountain wind farm and its suppression strategy were studied in detail.Because of increasing the number of wind turbines in wind farm,the power grid system impedance would be changed.This paper firstly calculated resonance frequency by accurate mathematical model,secondly used the active damping control strategy to design the controller,finally solved the problem of grid resonance.By MATlab simulation and practical application in large-scale mountain wind farm,the effectiveness and advantages of grid resonance suppression strategy were verified.
作者 余业祥 刘江华 付斌 Yu Yexiang;Liu Jianghua;Fu Bin(Dongfang Electric Wind Power Co.,Ltd.,Deyang Sichuan,618000)
出处 《东方汽轮机》 2019年第1期73-78,共6页 Dongfang Turbine
关键词 风力发电机组 电网谐振 有源阻尼 PI控制器 LCL滤波器 wind turbine grid resonance active damping PI controller LCL filter
  • 相关文献

参考文献2

二级参考文献24

  • 1刘飞,段善旭,查晓明.基于LCL滤波器的并网逆变器双环控制设计[J].中国电机工程学报,2009,29(S1):234-240. 被引量:78
  • 2张宪平,林资旭,李亚西,许洪华.LCL滤波的PWM整流器新型控制策略[J].电工技术学报,2007,22(2):74-77. 被引量:44
  • 3赵清林,郭小强,邬伟扬.单相逆变器并网控制技术研究[J].中国电机工程学报,2007,27(16):60-64. 被引量:249
  • 4Marco Liserre, Frede Blaabjerg, Steffan Hansen. Design and control of an LCL-filter based three-phase active rectifier[J]. IEEE Transactions on Industry Applications, 2005, 41(5): 1281-1291.
  • 5Marco Liserre, Antonio Dell'Aquila, Frede Blaabjerg. Genetic algorithm based design of the active damping for a LCL-filter three-phase active rectifier[J]. IEEE Transactions on Power Electronics, 2004, 19(1): 76- 86.
  • 6Lindgren M, Svensson J. Connecting fast switching vlotage-source converters to the grid-harmonic distortion and its reduction[C]. IEEE Strock Power Tech Conference, Stockholm: Proceedings of Power Electronics, 1995: 191-195.
  • 7Mariusz Malinowski, Wojciech Szczygiel, Marian P Kazmierkowski, et al. Simple sensorless active damping solution for three-phase PWM rectifier with LCL filter[C]. IECON 2005, 32nd Annual Conference of IEEE, 2005: 5.
  • 8Marco Liserre, Antonio Dell'Aquila, Frede Blaabjerg. Stability improvements of an LCL-filter based three- phase active rectifier[C]. PESC Record-IEEE Annual Power Electronics Specialists Conference, 2002, 3: 1195-1201.
  • 9Liserre M, Blaabjerg F, Chiarantoni E. A stable three-phase LCL-filter based active rectifier without damping[C]. Conference Record-IAS Annual Meeting IEEE Industry Applications Society, 2003, 3: 1552- 1557.
  • 10Marco Liserre, Frede Blaabjerg, Remus Teodorescu. Grid impedance detection via excitation of LCL-filter resonance[C]. Industry Applications Conference, Fourtieth IAS Annual Meeting. 2005, 2: 910- 916.