摘要
对一起特高压变电站1000kVGIS绝缘故障的实例进行分析,介绍了绝缘故障的定位和分析方法,结合保护动作情况、故障录波信息以及SF6气体分解物检测等多种手段确定了故障气室,对故障气室进行返厂解体检查,找到了故障的发生原因,并提出了相应的防范措施。
An example of insulation fault in 1 000 kV GIS of UHV substation is analyzed.The location and analysis method of insulation fault are introduced.The fault gas chamber is determined by means of protection action,fault recording information and SF6 gas decomposition detection etc.The failed gas chamber is checked after it is returned to the factory and disassembled,the cause of the fault is found,the corresponding preventive measures are put forward.
作者
安滨
AN Bin(Maintenance Company of State Grid Shandong Electric Power Co.,Ltd.,Jinan 250118,Shandong Province,China)
出处
《电力安全技术》
2019年第7期31-35,共5页
Electric Safety Technology
关键词
特高压变电站
GIS设备
绝缘故障
故障定位
解体检查
UHV substation
GIS equipment
insulation failure
fault location
disassembly inspection