变压器区内故障并联补偿电容器谐波电流对差动保护的影响 被引量:1

Influence of Harmonic Current in Parallel Compensation Capacitor on Differential Protection in Transformer Inside Fault
下载PDF
导出
摘要 某220kV降压变压器在低压侧差动保护区内故障时,两套不同制动原理的纵联差动保护出现了不同的动作行为。通过对保护装置故障录波数据的离线分析计算,发现了相间故障时,低压侧并联补偿电容器的自由振荡谐波电流对变压器纵联差动保护的影响原因。分析了故障期间并联补偿电容器的谐波电流产生原因及幅频特性,并提出了对差动保护原理的改进建议。 When a failure occurs in the low voltage side differential protection zone of a 220 kV step-down transformer,two sets of longitudinal differential protection act differently on different breaking principles. According to offline analyses and calculations with MATLAB software upon protection device recorded wave data,it has been found why free oscillation of the harmonic current of the low voltage side parallel compensation capacitor impacts the transformer longitudinal differential protection when inter-phase fault occurs.Also,an analysis is made of the cause of generation of harmonic current and its amplitude frequency characteristics of the parallel compensation capacitor during the fault.Suggestions for improvement of the differential protection principles are also made.
出处 《电力系统自动化》 EI CSCD 北大核心 2015年第8期159-163,共5页 Automation of Electric Power Systems
关键词 变压器保护 差动保护 故障录波 谐波电流 故障分析 transformer protection differential protection fault recording harmonic current fault analysis