摘要 对空气预热器低温腐蚀进行详细分析 ,找出空气预热器发生堵灰的根本原因在于烟气中存在SO3以及受热面金属壁温低于烟气露点。对此 ,提出了提高受热面壁温在烟气露点以上等控制措施 。 Detailed analysis of low temperature corrosion in regenerative air heaters had been carried out, it was found that the basic causes leading to ash-clogging in the said air heaters were: (1) SO 3 existing in the flue gas; (2) the wall temperature of heating surface was lower than dew point of the flue gas. For these reasions, some control measures for enhancing wall temperature of the heating surface were put forward, so as to ensure the normal operation of the said air heaters.
机构地区 华能丹东电厂
出处 《热力发电》 CAS 北大核心 2002年第5期46-49,共4页 Thermal Power Generation
  • 相关文献

参考文献3

  • 1-.石家庄热电厂220t/h锅炉水膜除尘器《GSH-220型除尘脱硫工程设计方案》[M].河北电力设备厂,1999..
  • 2-.化学工程手册(3)[M].化学工业出版社,1998..
  • 3-.石家庄热电厂12号炉除尘器性能试验[M].河北电力试验研究所,1999..