摘要
介绍大武口电厂采用反渗透化学除盐联合处理工艺对原除盐系统进行技术改造的情况 ,其中包括系统设计、调试、运行中的技术关键。该系统已运行 4年 ,反渗透系统的脱盐率仍保持在98%以上。
The technical retrofit of original water-demineralizing system by using combined treatment of reverse-osmosis and chemical desalting in Dawukou Thermal Power Plant has been descrebed, including key technical points in system design, commissioning test and operation. The retrofitted system has been put into operation for four years, the desalting rate of the reverse-osmosis system still remains 98% and above.
出处
《热力发电》
CAS
北大核心
2002年第5期83-85,89,共4页
Thermal Power Generation