摘要
以往主泵区域火灾探测设备有两种——红外火焰探测器和吸气式感烟探测器。在近几年的维护过程中,红外火焰探测器故障率高。因此,取消了红外火焰探测器,改为两台吸气式感烟探测器双独立运行模式,避免以往高温高辐射环境对主设备的影响,增加了火灾设备的使用寿命,降低了维护成本。实施至今近两年时间,1、2号机组主泵间火灾探测运行稳定。
There are two kinds of the fire detection equipment in the primary pump house.One is infrared flame detector,the other one is aspiration smoke detection.But the failure rate of infrared flame detectors is high in recent years.So we dismantling the infrared flame detectors and replace them by aspiration smoke detection.This avoids the influence of high temperature and high radiation on equipments,increases the service life of fire equipment and reduces the maintenance cost.
作者
干炯申
张瑞华
周焕
Gan Jiongshen;Zhang Ruihua;Zhou Huan(Maintenance Three Office of China Nuclear Power Operation Management Co.,Ltd.,Zhejiang,Haiyan,314300,China)
出处
《仪器仪表用户》
2019年第4期63-67,共5页
Instrumentation
关键词
主泵区域
火灾探测
吸气式感烟探测器
红外火焰探测器
冗余
primary pump house
fire detection
aspiration smoke detection
infrared flame detector
redundancy