摘要
介绍江西省电容补偿装置串联电抗器的电抗率均选用 6 % ,这种配置在 2 2 0kV变电站中较容易引起三次谐波放大甚至谐振 ,从三次谐波放大事故实例 ,分析谐波放大机理 ,提出抑制谐波放大的方法。
In this paper reactance rate of condenser compensation apparatus series reactor selection 60 percent which leaded to easily to third harmonic amplification so far as to resonate are introduced. Analysis harmonic amplification mechanism? preuention methods are put foward.
出处
《江西电力》
2002年第4期4-8,共5页
Jiangxi Electric Power