摘要
针对启动1号给水泵时,1号发电机-变压器组差动保护有时会误动的情况,经过分析和计算,确认1号高压厂用变压器高压侧电流互感器C相二次出线IC441与ICN441接反,是造成差动保护误动的直接原因,经验证无误后,恢复了IC441与ICN441的正确接线,消除了主设备的主保护长期遗留下的事故隐患。
When start up No.1feed water pump ,the differential relay protection of No.1generator-trans-former set may happen misoperation.By analysis and calculation,it is confirmed that the secondary out puts I C441 and I CN441 on phase C of the current transformer at high voltage side of No.1high voltage transformer are reversedly connected.After in spection and verification,the mistake is corrected.
出处
《电力自动化设备》
EI
CSCD
北大核心
2002年第11期83-84,共2页
Electric Power Automation Equipment
关键词
给水泵
机组
误跳闸
故障分析
火力发电厂
differential relay protection
fault analy sis
prevention strategy