期刊文献+

电力系统通信的不中断供电电源

The uninterrupted power supplying system for electric power telecommunication
下载PDF
导出
摘要 通过对电力系统通信电源的特点、现状和问题的分析,提出了采用"交流单母线分段"和"直流双母线分段"的接线方式、按"(N-1)的稳定规则"配置系统的功能单元、以"(1+1)双回路"对通信设备供电的方案,并介绍了电力系统通信不中断供电电源成套设备的原理、元器件选择、组屏及组屏工艺。 This paper analyses the characters and current situation of the power supplying system for electric power telecommunication and discusses the problem existing in the power supplying system.Then puts forward the power supplying and distributing scheme of 'AC unigeneratrix subsection' and 'DC bigeneratrix subsection'.Under the reliability rule of 'N-1'and '(1+1) protection power supplying method',this paper discusses how to configure the power supplying system for electric power telecommunication.This paper also introduces the principle,the selection of parts,configuration and technology of the uninterrupted power supplying system for electric power telecommunication.
作者 朱发强
出处 《电力系统通信》 2002年第11期33-38,共6页 Telecommunications for Electric Power System
关键词 不中断供电电源 电力系统通信 供电电源 高可靠性 高稳定性 高可用性 通信电源 electric power telecommunication power supplying device high reliability high stability high usability
  • 相关文献

参考文献3

  • 1张廷鹏,吴铁军,徐明,张生舟.通信高频开关电源[M].北京:人民邮电出版社,1997.
  • 2孙向阳,刘永秋,任新明,李雷明.通信电源与空调及环境监控系统[M].北京:人民邮电出版社,1999.
  • 3GB/T 17246-1998 eqv IEC 1085,1992.电力系统通信业务导则[S].中华人民共和国电力部,1996.

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部