期刊文献+

换流变压器现场高压试验电晕分析及措施 被引量:1

Analysis of Onsite High-Voltage Test Corona in Converter Transformer and Measure
下载PDF
导出
摘要 在现场开展换流变压器交直流耐压、局部放电等高压试验时,高压电晕会对试验结果产生严重干扰,电晕损失也会增加试验电源的负担。结合±800 k V特高压直流工程建设实际,建立高压试验中防晕导线的模型,仿真分析在不同电压类型、不同电压等级、不同导线直径以及不同导线连接状况下试验线路上的场强分布状况,得出影响防晕导线最大场强的影响因素,并对防晕导线的对接结构进行改进,开发出了新型防晕导线。 When high-voltage tests of converter transformer such as alternating current and direct current withstand voltage and partial discharge were carried out on site, the high-voltage corona would seriously disturb the test results and the corona loss would increase the load of experimental power supply. Combined with ±800 kV extra-high voltage direct current practical engineering construction, this paper established the anti-corona wire model in high-voltage test. Simulation analysis was made to the field intensity topography of test circuits under the conditions of different voltage type, different voltage grade, different wire diameter and different wire connection, so as to obtain the influence factor on the maximum field intensity of anti-corona wire, improving the docking structure of anti-corona wire and developing new type of anti-corona wire.
作者 周海滨 刘婉莹 冯家伟 张新波 ZHOU Hai-bin;LIU Wan-ying;FENG Jia-wei;ZHANG Xin-bo(Test & Maintenance Center, China Southern Power Grid Extra High Voltage Power Transmission Company, Guangzhou 510663, China;School of Electric Power, South China University of Technology, Guangzhou 510640, China)
出处 《电工电气》 2017年第2期39-42,共4页 Electrotechnics Electric
关键词 电场强度 电晕 对接 防晕导线 electric field intensity corona docking anti-corona wire
  • 相关文献

参考文献2

二级参考文献4

  • 1马卫平,杨海军,郑良华,郝德志.500kV大型电力变压器现场局部放电试验[J].高电压技术,1995,21(1):53-55. 被引量:9
  • 2GB50150-1991.电气装置安装工程电气设备交接试验标准[S].[S].,..
  • 3胡启凡 曹利安 谢毓城.变压器试验技术[M].北京:机械工业出版社,2001,24(8).62-64.
  • 4朱德恒,严璋.高电压绝缘[M].北京:清华大学出版社,1986.

共引文献19

同被引文献5

引证文献1

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部