330kV同塔双回线路感应电压和电流的仿真研究 被引量:1

Simulation research of the induced voltage and current in 330 kV same tower double circuit transmission lines
下载PDF
导出
摘要 针对同塔双回线路中,一回线运行、另一回线停运检修时,在停运线路上产生的感应电压和电流是否威胁人身安全的问题,结合罗山—灵州330 kV输电线路实际工程,建立了基于电磁暂态分析程序ATP-EMTP的感应电压和电流仿真计算模型,计算分析了静电感应和电磁感应2种类型的电压和电流。仿真结果表明:330 kV同塔双回线路一回线运行、另一回线停运检修时,停运线路上感应产生的电压、电流幅值远远超过人体的安全电压和安全电流,需对线路接地开关进行正确选择。 Aiming at the problem that when double circuit transmission lines on the same tower,one circuit is operating,and the other is stopping to overhaul,the induced voltage and circuit on the shutdown line whether menace personal safety for maintenance personnal,Combining with Luoshan-Lingzhou330kV transmission line project,establishes the induced voltage and circuit simulation calculation model based on electromagnetism transient analysis program(ATP-EMTP),calculates and analyzes the electrostatic induction voltage and current and electromagnetic induction voltage and current.The simulation result shows that when double circuit transmission lines on the same tower,one circuit is operating,and the other is stopping to overhaul,induced voltage and current on the shutdown line far exceed the humans body safe voltage and current,so need to correctly select the ground switch for line.
作者 郭海斌 杨丽娟 GUO Haibin;YANG Lijuan(Ningxia Hui Autonomous Region Power Design Institute, Yincuan Ningxia 750001, China)
出处 《宁夏电力》 2017年第2期23-27,共5页 Ningxia Electric Power
关键词 330kV同塔双回线路 接地开关 电磁感应 静电感应 330 kV double circuit transmission line on the same tower ground switch electromagnetic induction electrostatic induction
  • 相关文献

参考文献9

二级参考文献53

共引文献190

同被引文献3

引证文献1

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部