摘要 针对一起220k V电缆终端击穿故障,结合解剖检查,笔者分析认为,故障原因为应力锥安装工艺质量不佳,造成应力锥与电缆接触面位置存在局部放电,持续作用下造成电缆绝缘和应力锥绝缘老化且绝缘强度下降,最终导致电缆击穿,由此提出相应的防范措施。 This paper analysed a terminal breakdown accident of a220kV cable.Based on the strpped and checkedterminal,the reason of cable breakdown was caused by the poor quality of installation technology which result of partial discharge between stress cone and the interface of power cable.The insulation strength of power cable and stresscone was reduced by the continued partial discharge with the aging of parts.Preventive measures were proposed.
作者 庞锴 白银浩 刘博 Pang Kai;Bai Yinhao;Liu Bo(State Grid Henan Electric Power Research Institute,Zhengzhou Henan 450052;Henan EPRI Gaoke Group Co., Ltd.,Zhengzhou Henan 450052)
出处 《河南科技》 2017年第11期70-72,共3页 Henan Science and Technology
关键词 电缆终端 应力锥 绝缘击穿 power cable’s terminal stress cone insulation breakdown
  • 相关文献

参考文献1

二级参考文献4

  • 1GB50168-2006电气装置安装工程电缆线路施工及验收规范[S].
  • 2周泽存.高电压技术[M].北京:中国电力出版社,2005:98-100.
  • 3饶文兵.珠海发电厂220kV电缆GIS端故障原因分析科学技术报告[R].国家电网武汉高压研究所,2008.
  • 4朱宏峰,谢海滨.一起高压电缆终端炸裂事故分析[J].电力安全技术,2011,13(2):24-27. 被引量:4