摘要
中国移动上海公司某数据机房存在明显的局部热点,通过普通手段无法消除。经过对该机房的深入研究,通过在机房回风口安装风机提高热点区域回风管回风静压的方式提高回风量,有效降低机房热点区域温度并达到机房要求。通过本改造方案为在用老机房局部热点改造提供了一些思路。
One Shanghai Mobile data room has obvious regional hotspots which can’t be eliminated by ordinary means.Through the in-depth study of the communication room,by Installing return EC-fans inside return ducts to increase return air static pressure around the regional hot spot,this way can increase the return air fl ow and effectively reduce the regional hotspots‘temperature and reach design requirements.This reform program provide one good idea for eliminating regional hotspot problems in using communication rooms.
作者
翁振邦
WENG Zhen-bang(Shanghai Stock Data Service Co., Ltd., Shanghai 201201, China)
出处
《电信工程技术与标准化》
2017年第9期64-67,共4页
Telecom Engineering Technics and Standardization
关键词
在用机房改造
局部热点
静压
节能
EC风机
usingcommunication rooms reform
regional hotspot
static pressure
energy saving
EC-fan