摘要
在一起非典型500 k V线路保护电流二次回路的相间短路故障中,由于短路电阻的存在,导致短路的两相电流出现了换相现象。通过对故障现象进行分析,结合理论计算出短路电阻大小,并借助PSCAD建模加以验证。根据仿真结果分析了短路电阻大小对短路电流的影响,为运维检修人员处理类似缺陷提供了参考。
This paper presents an untypical instance of phase-to-phase short-circuit fault in secondary current fault of500kV line protection.During to the short circuit resistance,the phases of the short-circuit current were inverted.By observation and analysis,the value of fault resistance is calculated,and the phenomenon is verified by PSCAD modeling.The influences of short-circuit resistance on short-circuit current is analyzed by simulation result,which can be referenced by operation and maintenance engineers in dealing with similar defects.
作者
田洪磊
王一
吕旭东
张松
黄超
TIAN Honglei;WANG Yi;LYU Xudong;ZHANG Song;HUANG Chao(State Grid Zhejiang Maintenance Branch Company, Hangzhou 311232, China)
出处
《浙江电力》
2017年第11期12-15,66,共5页
Zhejiang Electric Power
关键词
电流二次回路
相间短路
短路电阻
故障分析
继电保护
secondary current circuit
interphase short circuit
short-circuit resistance
fault analysis
relay protection