基于多频测相和行波测距法的电缆故障定位方法 被引量:8

Cable Fault Location Method Based on Multi-frequency Phase Measurement and Traveling Wave Distance Method
下载PDF
导出
摘要 借鉴于相位法激光测距的原理,提出一种利用多频行波的相位差对电缆进行故障定位的方法,即通过对比不同频率的发射信号与故障点反射信号之间的相位差得到故障点位置;并给出频率的确定方法。针对该方法对SIMULINK平台搭建的电缆故障模型在不同故障类型下进行仿真,结果表明电缆故障定位的相对误差能达到1%以下,证明了该方法的可行性。 A cable fault location method is proposed by using the phase difference of the multi-frequency traveling wave,that is,by comparing the phase difference between the transmission signal and the fault point reflection signal at different frequencies.And the way how to choose the frequencies is also proposed.According to this method,the cable fault model built on SIMULINK platform is simulated under different fault types and the simulation results show that the relative error rate of the cable fault location can be reduced to1%or less by using the phase method,which proves the feasibility of the method.
作者 卫永琴 张琦 西沙 WEI Yongqin;ZHANG Qi;XI Sha(College of Electrical Engineering and Automation, Shandong University of Science and Technology, Qingdao 266590, P.R.China)
出处 《科学技术与工程》 北大核心 2017年第36期184-188,共5页 Science Technology and Engineering
基金 国家自然科学基金(61471224) 青岛经济技术开发区科技发展计划(2014-1-25)资助
关键词 电缆故障 相位法 多频测相 MATLAB仿真 cable fault phase method multi-frequency phase measurement MATLAB simulation