某电厂#2发电机机端TV一次熔断器出现渐熔现象,通过对TV二次电压降低、故障熔断器温度升高等现象的分析,现场技术人员锁定故障点并制定合理的继热措施,在不停机的状态下完成故障熔断器的更换。
Gradual fusing occurred at#2 generator′s TV primary fuse in a power plant.By analyzing such phenomena as TV secondary voltage reduction and temperature rising of the fault fuse,the technical personnel made sure the fault point and took reasonable relay and thermotechnical measures,and then completed the replacement of the fault fuse in the condition of non-stop generating.
作者
胡文波
李博
孟庆党
王昱
HU Wenbo;LI Bo;MENG Qingdan;WANG Yu(Huaneng Chaohu Power Plant Co.,Ltd.,Chaohu 238015,China)
出处
《安徽电气工程职业技术学院学报》
2018年第1期7-10,共4页
Journal of Anhui Electrical Engineering Professional Technique College
关键词
发电机
电压互感器
不停机
励磁调节器
熔断器
generator
voltage transformer
non-stop generating
field regulator