期刊文献+

220kV电铁线路重合闸异常分析及解决措施

Analysis and Countermeasures for Reclosing Abnormality of 220kV Electrified Railway Line
下载PDF
导出
摘要 本文针对一起220kV电铁线路重合闸多次动作事件,从保护动作时序、录波、重合闸逻辑、操作箱回路四个方面进行分析,判断出弹簧操作机构储能时间与重合闸充电时间失配,是导致重合闸误判并多次动作的主要原因。然后探讨不同工况下重合闸的相关问题,并提出解决措施,以进一步提高重合闸的可靠性。 Considering a case of reclosing abnormality of 220kV electrified railway line,four aspects,i.e.the protection action order,waveform,reclosing logic and the secondary circuits of the operation box,were analyzed in this paper.It was pointed out that the main reason for reclosing abnormality was the time mismatch between the energy storage time of the spring operation mechanism and the charge time of the reclosing device.A series of measures which improve the reliability of reclosing devices were proposed by discussing the different working conditions of reclosing abnormality.
作者 谢志杰 林宏彬 蒋祖立 XIE Zhijie;LIN Hongbin;JIANG Zuli(State Grid Quanzhou Power Supply Company,Quanzhou 362000,China)
出处 《电工技术》 2018年第2期42-44,共3页 Electric Engineering
关键词 重合闸 时间失配 储能 开入 reclosing time mismatch energy storage enter
  • 相关文献

参考文献7

二级参考文献71

共引文献75

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部