数据机房风冷式冷水机组系统改造 被引量:2

System transformation of air-cooled chiller on data room
下载PDF
导出
摘要 针对数据机房单独使用风冷式冷水机组容易产生热岛效应,影响数据中心的安全稳定运行问题,提出在风冷式冷凝器后直接串联水冷式冷凝器的方法。利用软件EVAP-COND和Coolselector2设置一套数值计算方法进行计算,结果表明,系统改造后,在工作环境温度为45℃时串联系统的高压值为1.95MPa,随着工作环境温度的升高,高压值增大,在工作环境温度达到65℃时,串联系统的高压值为2.38MPa,均低于2.60 MPa的高压报警值,有效地避免机房主机在高温环境下因高压报警而停机的现象。 The air-cooled chiller is easy to produce heat island effect,which affects safe and stable operation of the data center.The water-cooled condenser is connected after the air-cooled condenser in this system.A set of numerical calculation method is established using EVAP-COND and Coolselector2 software,the result shows that when the system is transformed,high pressure of the series system is 1.95 MPa at the work temperature of 45℃.The high pressure increases with the increase of the work temperature.The high pressure of the series system is 2.38 MPa at the work temperature of 65℃,all below the high pressure alarm value(2.60 MPa),which is effective to avoid the system being shut down due to reaching the high pressure alarm value in high temperature environment.
作者 周宇 Zhou Yu(Shandong Jianzhu University)
机构地区 山东建筑大学
出处 《制冷与空调》 2018年第3期58-60,共3页 Refrigeration and Air-Conditioning
关键词 数据机房 系统改造 水冷式冷凝器 数值模拟 data room system transformation water-cooled condenser numerical simulaAion