期刊文献+

机房空调流体分布建模研究

Modeling Base on the Distribution of Machine Room Air Conditioners
下载PDF
导出
摘要 能源合理利用可以降低能耗,提高效率,因此需要对机房空调流体进行模拟和研究。根据高度、温度、风速和距空调位置几个参量,利用Matlab数学软件、第二型曲面积分、Simple算法、线性回归、k~ε两方程紊流模型,建立室内空气浓度分布图和室内热流量分布状况,整合机柜任务量对温度极值点的权向量,得出机柜任务量与温度的相关度及最低温度分配方案。数据分析表明:通过控制空调的冷通道出风口风速可以调节室内温度,并确定在不同任务量条件下最优空调送风速度和送风温度方案。 If energy is used rationally,energy consumption and efficiency can be reduced.Therefore,it is necessary to simulate and study the air conditioning fluid in the equipment room.Based on several parameters such as height,temperature,wind speed and air conditioning position,Matlab mathematical software,second type surface integral,SIMPLE algorithm,linear regression,two-equation turbulence model are used to establish the indoor air concentration distribution map and Indoor heat flux distribution.We integrate the weight vector of the equipment cabinet with the extreme value of the temperature and obtain the correlation between the task of the equipment cabinet and the temperature and the distribution scheme of the minimum temperature.The data analysis shows that the temperature of the indoor air can be adjusted by controlling the wind speed of air outlet of the cold air in the air conditioner,and the optimal air distribution rate and air supply temperature of the optimal allocation scheme under different task conditions are clarified.
作者 赵盟 张建蓉 ZHAO Meng;ZHANG Jian-rong(Faculty of Metallurgical and Energy Engineering,Kunming University of Science and Technology,Kunming 650093,China)
出处 《软件导刊》 2018年第4期58-63,共6页 Software Guide
关键词 机房空调 MATLAB软件 SIMPLE算法 线性回归 k~ε两方程紊流模型 equipment room air conditioning Matlab simple algorithm linear regression two-equation turbulence m
  • 相关文献

参考文献7

二级参考文献24

  • 1林素菊,刘小兵,苏华,温晓军.高大空间分层空调室内气流的数值模拟[J].制冷与空调(四川),2005,19(1):4-6. 被引量:20
  • 2雷晓维.自然散热条件下的机柜机箱的计算机辅助热设计计算[J].声学与电子工程,1995(1):37-42. 被引量:1
  • 3叶欣,蒋修英,沈国民.Airpak软件在气流组织领域的应用[J].应用能源技术,2006(10):45-47. 被引量:32
  • 4Nakao M,Hayama H, Uekusa T, An efficient cooling system for telecommunication equipment rooms [ C ] //Proceedings of the 10th International Tele-communications Energy Conference. San Diego, Canada: [ s. n, ], 1988: 344-349.
  • 5Maeda Y, Seshimo Y, Okazaki T, Study of a cooling system for the telecommunication base site [ J ]. ASHRAE Transactions,2005,111 (2) : 746-755.
  • 6Choi J ,Jeon J, Kim Y. Cooling performance of a hybrid refrigeration system designed for telecommunication eqmpment rooms [ J ]. Applied Thermal Engineering, 2007,27 ( 11/12 ) :2026-2032.
  • 7Sven Reichrath, Tom W Davies. Using CFD to model the internal climate of green houses:past, present and future [ J ]. Agronomie, 2002 (22): 3-19.
  • 8Ould Khaoua S A, Bournet P E, Migeon C, et al. Analysis of greenhouses ventilation efficiency based on computional fluid dynamics [ J ]. Biosystems Engineering, 2006, 95 (1) :83-98.
  • 9Mark Chown. Building simulation as an aide to design [ C ]// Eighth International IBPSA Conference. Eindhoven. Netherlands : [ s. n. ] ,2003 : 11-14.
  • 10爱默生网络能源解决方案[Z].2009.