200kV高压直流断路器操作拒动故障原因分析及建议 被引量:3

Causes Analysis and Suggestions on Operation Rejection Failure of 200kV HVDC Circuit Breaker
下载PDF
导出
摘要 高压直流断路器是多端柔性直流输电工程换流站内重要的电气设备,直接关系到柔直系统运行的可靠性。根据±200 k V高压直流断路器在系统操作合闸过程中,出现的位置信号未及时返回控制系统,断路器后序无法进行分闸操作的故障现象,经报文分析判断和现场故障检测,得出故障原因是断路器开关内极柱分位传感器位置偏移,造成分位信号响应延迟、断路器拒动。最后通过将分位传感器调整至正常工作位置的方法解决了该问题,并提出了需要制定高压直流断路器检修规程及监控后台增加断路器操作次数统计功能的建议。 HVDC circuit breaker is important electrical equipment in the converter station of multi-terminal flexible direct current transmission project,which is directly related to the system operation reliability.Ac-cordingtothefaultthatthepositionsignalof±200 kVHVDCcircuitbreakerdoesnotreturntothecontrol system in time during the operation and closing process of the system,the circuit breaker cannot be opened afterwards.Through messaging analysis and field fault detection,it is found that the fault reason is the displacement of the pole quantile sensor in the breaker switch,which results in the quantile signal response delay and operation rejection of circuit breaker.Finally,the problem is solved by adjusting the quantile sensor to the normal working position,and some suggestions are put forward that the maintenance rules of HVDC circuit breakers should be established and the statistical function of the operation times of the circuit breakers should be increased by monitoring and controlling backstage.
作者 张吼 杨勇 许琤 詹志雄 袁杰 ZHANG Hou;YANG Yong;XU Cheng;ZHAN Zhixiong;YUAN Jie(Grid State Zhoushan Power Supply Company,Zhoushan Zhejiang 316000,China)
出处 《浙江电力》 2018年第2期48-52,共5页 Zhejiang Electric Power
关键词 多端柔性直流 高压直流断路器 拒动 分位传感器 multi-terminal flexible direct current HVDC breaker operation rejection quantile sensor
  • 相关文献

参考文献8

二级参考文献87

共引文献382

同被引文献52

引证文献3

二级引证文献17

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部