换流变压器套管TA极性的正确与否直接关系到电流差动保护动作的可靠性,对换流变压器的安全稳定运行具有重要影响。针对常规TA极性校验方法难以用于换流变压器套管TA极性校验的问题,提出了一种改进的单相双绕组换流变压器套管TA极性校验方法,并将该方法应用到工程实践,应用结果表明,该方法正确有效。
The correctness of TA polarity of converter transformer bushing is directly related to the reliability of current differential protection,which has an important influence on the safe and stable operation of converter transformer.For conventional TA polarity checking method is difficult to be used for TA polarity verification of converter transformer bushing,an improved TA polarity checking method of single-phase double-winding converter transformer bushing is proposed and applied to engineering practice.Engineering practice shows that the method is correct and effective.
作者
张富超
芮建勋
武曹军
张富春
张丽丽
ZHANG Fuchao;RUI Jianxun;WU Caojun;ZHANG Fuchun;ZHANG Lili(Hebei Power Transmission & Transformation Co.,Ltd., Shijiazhuang 050051, China;Qinhuangdao Electric Power Company, Qinhuangdao 066000, China)
出处
《内蒙古电力技术》
2018年第2期69-71,78,共4页
Inner Mongolia Electric Power
关键词
换流变压器
套管TA
极性校验
网侧绕组
阀侧绕组
converter transformer
bushing current transformer
polarity checking
grid winding
valve winding