高层办公建筑新风系统调查与设计分析 被引量:3

Analyze of Fresh Air System Design in High-rise Office Building
下载PDF
导出
摘要 本文通过对部分高层办公建筑实测分析,发现部分办公区存在室内CO_2浓度超标、冬季空气相对湿度过低、夏季空气温度湿度过高、室内噪声值超标等的问题。并在调查中观察到办公区新风系统经常不开或间歇开启,空调(供暖)季节开窗、开门现象普遍,造成室内新风量不足,空调能耗增加。基于此调查结果,建议新风系统设计应合理划分新风系统、设计室内气流组织、准确计算新风量、正确设置新风机、有效地使用节能节支措施,使新风系统设计合理、高效。 There are some problems of indoor CO 2 concentration,winter relative humidity,summer air temperature humidity,indoor noise value and so on in highrise office building.Besides,the fresh air system work occasionally during operating season.Therefore it’s common to see the door and window kept opening in operating season so as to get fresh air which would surely increase energy consumption.In order to make fresh air system reasonable and effective,the paper strongly recommended that the design of fresh air system should be more accurate.Such as accurate calculation of fresh air volume,reasonable design of fresh air handling unit,effective taking energy conservation measures.
作者 贺永良 HE Yong-liang(China Railway 18 Bureau Group Fourth Engineering Co.,Ltd.)
出处 《建筑热能通风空调》 2018年第6期71-74,6,共5页 Building Energy & Environment
关键词 内温湿度 CO2浓度 人员习惯 新风系统设计 indoor air temperature and humidity CO2 concentration human behavior design of fresh air system
  • 相关文献

参考文献1

二级参考文献12

  • 1Sundell J. On the history of indoor air quality and health[ J]. Indoor air, 2004,14:51-58.
  • 2Hazim B, Awbi. Chapter7-ventilation [ J ]. Renewable and sustainable energy reviews, 1998,2 : 157-188.
  • 3ASHRAE. ASHRAE Standard 62.1-2007: Ventilation for Acceptable Indoor Air Quality [ S ]. Atlanta: ASHRAE,2007.
  • 4Yaglou C. P. Ventilation requirements [ J ]. Trans. ASHVE, 1936,42 : 133-162.
  • 5John E, Janssen, P.E. The V in ASHRAE: An historical perspective [ J ]. ASHRAE Journal, 1994, 8 :126-132.
  • 6Bjame W, Olesen. International development of standards for ventilation of buildings [ J ]. ASHRAE Journal, 1997, 4:31-39.
  • 7Steven Taylor. Determining ventilation rates: Revisions to Standard 62-1989[J]. ASHRAE Journal, 1996, 2: 126-132.
  • 8Dennis Stanke. The new ventilation rates in standard 62.1-2004 [ J ]. IAQ Applications, 2006,9-11.
  • 9Jokl M. V. Evaluation of indoor air qualtiy using the decibel concept based on carbon dioxide and TVOC [ J]. Building and Environment, 2000, 35:677-697.
  • 10中国建筑科学研究院.GB50368-2005住宅建筑规范[S].北京:中国建筑工业出版社,2005.

共引文献4

同被引文献17

引证文献3

二级引证文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部