摘要
基于锂离子电池的热失控过程设计实验,分析充放电电流为0.5C、1C、2C、3C时锂离子电池热失控过程的温度变化特征。在此基础上自主研发针对18650型锂离子电池及电池组的热失控三级预警装置。为验证装置的有效性,开展锂离子电池外部短路、低阻值放电实验,结果表明,该装置在应对异常升温的锂离子电池时显示出优良的预警性能,能满足对18650型锂离子电池火灾爆炸预警工作的要求。
Experiments were designed based on thermal runaway process of the lithium ion battery,the characteristics of the temperature change in the process when the charge and discharge current was 0.5C,1C,2C and 3C separately were analyzed.A three-level warning device for thermal runaway of 18650 lithium ion battery was developed.In order to verify the effectiveness of the device,external short-circuit and low resistance discharge experiments of the lithium ion battery was made.The results showed that the device shows excellent early warning performance in dealing with abnormal heating of lithium ion batteries,and can meet the requirements for the early warning of fire and explosion of type 18650 lithium ion batteries.
作者
杨赟
刘凯
陈翔宇
王志荣
王苏盼
YANG Yun;LIU Kai;CHEN Xiang-yu;WANG Zhi-rong;WANG Su-pan(Safety science and engineering,Nanjing University of Technology,Jiangsu Nanjing 210009,China)
出处
《消防科学与技术》
CAS
北大核心
2018年第7期939-942,共4页
Fire Science and Technology
基金
江苏省"六大人才高峰"高层次人才计划项目(2014-XNY-007)
江苏省科技项目"锂离子电池组热失控预测预警与防控关键技术研发与应用"(BE2016771)
关键词
锂离子电池
热失控
火灾
火灾报警
lithium-ion battery
thermal runaway
fire
fire alarm