期刊文献+

济南地区地铁车站地震响应数值分析

Numerical Analysis of the Shallow-buried Subway Station Seismic Response in Jinan City
下载PDF
导出
摘要 利用有限差分软件FLAC^(3D)5. 0,以大杨庄地铁车站为工程背景,建立三维抗震动力模型,并通过在基岩处输入3条人工地震波H1、H2、H3,分析了动力作用下地层中峰值加速度规律及车站主体的结构变形及内力响应规律。计算结果显示:越接近地表,地层中的峰值加速度越大;车站结构整体侧向位移呈现倒三角形状;车站结构的侧墙、中柱与各楼层板的连接处,承受较大内力,是整个车站结构抗震的薄弱部位。 The finite element software FLAC3D5.0 is used to establish a 3D seismic dynamic model based on the engineering of Dayangzhuang Station in Jinan metro.In order to analyze the rules of peak acceleration in the stratum,the deformation of station main structure and the internal force response under soil structure interaction,three artificial seismic waves H1,H2,H3 are inputted in the bedrock respectively.The simulation results reveal that the peak acceleration in the stratum becomes greater when it is closer to the surface;the overall lateral displacement of the station structure presents an inverted triangle mode;as the seismic weak places in the whole subway structure,the joints among side walls,central columns and floor plates bore relatively larger internal forces.
作者 商金华 毛荣吉 王晓昱 SHANG Jinhua;MAO Rongji;WANG Xiaoyu(Ji’nan Rail Transit Group Co.,Ltd.,250101,Ji’nan,China)
出处 《城市轨道交通研究》 北大核心 2018年第10期67-72,共6页 Urban Mass Transit
关键词 地铁车站 土-结构 结构变形 内力响应 subway station soil structure structural deformation internal force response
  • 相关文献

参考文献5

二级参考文献36

共引文献105

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部