摘要
AVC系统采用电压期望值作为连续可调无功源的控制指令值,由于各类连续可调无功源的调节速度存在差异,导致出现"抢无功"的现象,不利于电网安全经济优质运行。为解决这一问题,本文提出了一种AVC控制指令选择方法,即选择灵敏度高、调节速度快的连续可调无功源下发电压期望值作为控制指令,其余下发无功出力期望值作为控制指令。该方法与现有AVC系统结合,形成一套AVC控制指令选择系统,可有效解决"抢无功"问题,保证电网安全经济优质运行。
The existing AVC system uses the expected voltage value as the control command value of the continuous adjustable reactive power source.However,the phenomenon of"grabbing reactive power",which is caused by the difference in the adjustment speeds of various continuous adjustable reactive power sources,is not conductive to safe,economical and high-quality operation of the power grid.To solve this problem,a method of selecting AVC control command is proposed,in which the expected voltage value as control command is delivered to the the continuous adjustable voltage source with high sensitivity and fast adjustment speed and the expected reactive power is delivered to the rest.This method,combined with the existing AVC system,forms an AVC control command selection system to effectively solve the problem of"grabbing reactive power"and ensure safe,economical and high-quality operation of the power grid.
作者
周铁刚
吴晋波
何晓
熊尚峰
李敏
童争光
ZHOU Tiegang;WU Jinbo;HE Xiao;XIONG Shangfeng;LI Min;TONG Zhengguang(State Grid Hunan Electric Power Company Limited Shaoyang Power Supply Company,Shaoyang 422000,China;State Grid Hunan Electric Power Company Limited Research Institute,Changsha 410007,China)
出处
《湖南电力》
2018年第6期37-41,共5页
Hunan Electric Power
基金
国家电网公司科技项目(5216A018000Q)
国网湖南省电力有限公司科技项目(5216A515002V)
关键词
AVC
控制指令
连续变量设备
安全经济运行
AVC
control command
continuous variable equipment
safe and economical operation