高压开关柜绝缘事故分析及处理 被引量:9

Insulation Accident Analysis of High Voltage Switchgear and Its Treatment
下载PDF
导出
摘要 分析了高压开关柜易发生的短路、绝缘件受潮及表面脏污、电气安全距离小、高压设备对绝缘挡板放电、母排对套管放电、安装施工工艺不良等问题造成的绝缘故障,并提出清除开关柜污秽物、封堵间隙等开关柜绝缘处理措施。通过处理后,实际运行效果表明,开关柜设备运行稳定。 The insulation faults caused by short circuit,damp and dirty surface of insulators,small electrical safety distance,discharge of insulating baffle by high voltage equipment,discharge of bushing by poor installation and construction technology of high voltage switchgear cabinet were analyzed and summarized.The insulation treatment measures for switchgear cabinet such as removing contaminants and closing gap were put forward.The actual operation results showed that the switchgear operation was stable through the treatment.
作者 丘善棋 武霞 QIU Shanqi;WU Xia(Fujian Ruisen New Material Co.,Ltd.,Longyan364400,China;Inner Mongolia Construction Corporation,Hohhot010020,China)
出处 《内蒙古电力技术》 2018年第6期62-65,共4页 Inner Mongolia Electric Power
关键词 高压开关柜 绝缘故障 放电 接触电阻 有机硅封堵胶 high voltage switchgear insulation fault discharge contact resistance silicone plugging glue