开关死区(失灵)保护优化方案及测试应用 被引量:5

Breaker dead zone(failure) protection optimization scheme and test application
下载PDF
导出
摘要 对于传统交流电网,目前的继电保护技术已日臻成熟,但是随着特高压交直流混联电网的形成,交流保护对电网特性变化的适应性亟待提升。本文针对开关失灵或CT死区故障时保护切除故障时间长、可能引发多回直流连续换相失败、导致系统发生的严重后果,介绍了两种开关死区(失灵)保护优化方案,将开关失灵或CT死区故障时切除时间缩短至200ms以内,防止引发电网稳定破坏事故,并搭建了测试系统,对优化后的开关死区(失灵)保护的性能指标进行了详细考核,对系统中发生异常运行工况时开关死区(失灵)保护的动作情况进行了验证测试,从而保证优化后的开关死区(失灵)保护在电力系统中运行的稳定性和可靠性。 The relay protection technology is becoming more and more mature for the traditional AC power grid,but with the formation of UHV AC and DC hybrid power network,the adaptability of AC protection to the characteristics of the power grid needs to be improved.In view of the breaker failure or the CT dead zone fault,the removal of the fault time is long,which may lead to the failure of the multiple DC continuous commutation,resulting in the serious consequences of the system.In this paper,two kinds of breaker dead zone(failure)protection optimization scheme is introduced,which shortens the excision time to less than 200ms when the breaker failure or the CT dead zone fault is broken down to prevent accidents caused by power grid stability damage.And it builds a test system.The performance index of the optimized breaker dead zone(failure)protection is examined in detail,and the action situation of the breaker dead zone(failure)protection in the abnormal operation condition is verified and tested,so as to guarantee the optimized breaker dead zone(failure)protection operation stability and reliability in power system.
作者 乔彦涛 徐兴豫 于士谦 胡宝 Qiao Yantao;Xu Xingyu;Yu Shiqian;Hu Bao(XJ Electric Co.,Ltd,Xuchang,He'nan 461000)
出处 《电气技术》 2019年第1期97-100,105,共5页 Electrical Engineering
关键词 开关死区(失灵)保护 站域差动 测试验证 breaker dead zone(failure)protection substation area differential test verification
  • 相关文献

参考文献10

二级参考文献161

共引文献489

同被引文献46

引证文献5

二级引证文献17

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部