期刊文献+

容湿状态下加气混凝土砌块导热系数研究 被引量:2

Research on thermal conductivity of aerated concrete blocks under humidity
下载PDF
导出
摘要 加气混凝土是建筑围护结构常用的材料之一,但其吸湿性较强,在容积湿度(以下简称"容湿")影响下,导热系数会产生一定的变化.文章以南京地区为例,通过对加气混凝土外围护结构内外表面温度、热流密度的实测,结合计算推导,发现该地区墙体导热系数受容湿影响而增大,其修正系数为1. 132.研究简化了热湿传递过程,较为准确的推算出了加气混凝土围护结构在运营过程中的实际导热系数,有助于精确分析建筑运营过程中的能耗. Aerated concrete is one of the commonly materials used for building envelopes,but its hygroscopicity is strong. Under the influence of volumetric humidity( hereinafter referred as " humidity"),the thermal conductivity will change. Taking the Nanjing area as an example,the actual measurement of the inner and outer surface temperature and heat flux density of the aerated concrete surrounding structure is combined with the calculation. It is found that the thermal conductivity of the wall is increased by the humidity tolerance,and the correction coefficient is 1. 132. The study simplifies the heat and moisture transfer process,and accurately estimates the actual thermal conductivity of the aerated concrete retaining structure during operation,which helps to accurately analyze the energy consumption during the construction operation.
作者 于沈尉 王金奎 YU Shenwei;WANG Jinkui(School of Architecture and Art,Hebei Institute of Architectural Engineerin,Zhangjiakou 075000,China)
出处 《渤海大学学报(自然科学版)》 CAS 2018年第4期309-314,共6页 Journal of Bohai University:Natural Science Edition
基金 国家自然科学基金项目(No:51579028 No:51811530270) 冻土工程国家重点实验室开放基金(SKLFSE201604)
关键词 加气混凝土砌块 容湿 导热系数修正 aerated concrete block moisture tolerance thermal conductivity correction
  • 相关文献

参考文献7

二级参考文献27

共引文献53

同被引文献18

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部