期刊文献+

典型小电流接地故障实例及暂态选线分析 被引量:19

Analysis of typical earth faultsexample and transient feeder selection technology in the non-solidly earthed system
下载PDF
导出
摘要 目前对小电流接地故障特征的理论分析已较完善,但缺乏对现场典型小电流接地故障实例的认识及利用典型实例对选线技术的验证。介绍了暂态选线方法及原理,并根据现场选线装置实际记录的典型故障实例波形,分析并总结了典型接地故障的发生原因、故障特征及对暂态选线结果的影响。通过对现场典型小电流接地故障实例的分析与总结,有利于提高对现场典型接地故障特征的认识,验证暂态选线装置的可靠性。 The fault characteristic theoretical analysis in the non-solidly earthed network is almost complete.While the understanding of the typical field faults example and the verification of the faulty feeder selection technologies by field faults data are in great demand.The method and principle of transient faulty feeder selection technologies are introduced in this paper.According to the typical field faults waveforms,the cause of the typical field faults,the fault characteristic and the effect on the result of the transient faulty feeder selection technologies are analyzed.By analyzing and summarizing the typical field faults examples,the understanding of the typical field faults can be improved.The reliability of the transient faulty feeder selection technologies can be verified.
作者 李天友 王超 陈敏维 薛永端 黄建业 Li Tianyou;Wang Chao;Chen Minwei;Xue Yongduan;Huang Jianye(State Grid Fujian Electric Power Co.,Ltd.,Fuzhou 350003,China;Shandong Kehui Power Automation Co.,Ltd.,Jinan 250101,China;Electric Power Research Institute State Grid Fujian Electric Power Company,Fuzhou 350007,China)
出处 《电测与仪表》 北大核心 2019年第2期116-122,共7页 Electrical Measurement & Instrumentation
基金 国家自然科学基金资助项目(51477184) 国家电网公司科技项目(52130416000D)
关键词 小电流接地系统 单相接地故障 典型实例 暂态选线 non-solidly earthed network single-phase grounding fault typical field faults transient faulty feeder selection
  • 相关文献

参考文献15

二级参考文献122

共引文献739

同被引文献264

引证文献19

二级引证文献63

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部