摘要 针对一起500 kV HGIS外置式电流互感器受潮的案例开展分析,结合该类设备结构,找出了受潮原因,提出了防潮措施以及受潮电流互感器的干燥措施。通过案例的分析认及处理认为,该类型外置式电流互感器结构在户外运行时极易导致雨水进入,应加强密封;当电流互感器线圈受潮时,采用电加热和热风法相结合的方式能够取得较好的效果。 Based on the analysis of a damping defect of external current transformer of 500 kV HGIS,the reasons of damping are found out and the moisture-proof measures and drying measures are put forward for current transformer.Through the analysis and treatment of the case,it is believed that the rainwater can easily get into this type of external current transformer when it is running outdoors,and the sealing should be strengthened.When the coil of current transformer is damped,the combination of electric heating and hot air method can achieve wonderful results.
作者 唐静 罗洋 龙震泽 Tang Jing;Luo Yang;Long Zhenze(State Grid Sichuan Electric Power Research Institute,Chengdu 610041,Sichuan,China)
出处 《四川电力技术》 2018年第6期71-74,共4页 Sichuan Electric Power Technology
关键词 HGIS 外置式电流互感器 受潮 干燥措施 hybrid gas insulated switchgear(HGIS) external current transformer damping drying measures
  • 相关文献

参考文献4

二级参考文献19

  • 1徐世山,孟可风,刘文泉.一起363kVGIS充电闪络故障的原因分析[J].高压电器,2007,43(1):74-76. 被引量:37
  • 2[1]CIGRE WG 33/23.12 Insulation co-ordination of GIS: Return of experience, on site tests and diagnostic techniques. Electra No 176 Feb. 1998.
  • 3[2]CIGRE WG 15.03 Diagnostic Mothods for Cas Insulating systems. CIGRE Report 15/23-01 1992
  • 4[4]IEC 71-1 Insualtion Co-ordination part 1:Defintion, Principles and Rules 1993
  • 5[5]CIGRE WG 33/13.09. Very fast transient phenomenaassociated with gas insulated substations. CIGRE33-13 1988
  • 6[6]CIGRE WG. 15.03.Effects of particles on GIS lusufafion and the Evaluation of Belevant Diagrostic Tools. CIGBE Report 15~103 1994
  • 7[7]Sabot A, et al Taillebois GIS insulation co ordination: on-site tests and Dielectric diagnostic techniques, A util: ty point of view IEEE Transactions on power delivery, vol ll, No3, July 1996. Pp. 1309-1316
  • 8[8]IEC 517 Gas insulated metal enclosed switchgear for 72, 5kV and above.
  • 9[9]IEC 71-2 Insulation co-ordination Part 2: Application guide 1996
  • 10[10]Okabe S., Zaima E., Ishikawa T, yamagiwa T On-site detection of defect in GIS with PD measurement 9th-ISH Graz 1995

共引文献65