期刊文献+

某10 kV线路自动化开关误动作原因分析 被引量:1

Reason Analysis of Misoperation of Automatic Switch in a 10 kV Line
下载PDF
导出
摘要 某10 kV架空配电线路自动化开关发生误动作,经分析可知该开关误跳闸的原因是控制器电源转换模块烧毁。基于MATLAB仿真软件搭建了该开关控制器电源管理系统模型,进一步分析了电源转换模块烧毁原因。针对发现的问题,提出了控制器出口防误动作以及施工现场防误接线的建议,有效解决了此类型开关在工程实践过程中的误动作问题。 The misoperation of automatic switch in a 10 kV overhead distribution line happened and it is found by analysis that the reason of the switch misoperation is the burnt-out power converter module of the controller. The model of power management system of the switch controller is built based on MATLAB simulation software and the reason of the burnt-out power converter module is further analyzed. Aimed at problems found, suggestions against the misoperation of the controller outlet and the misconnection at construction site are proposed, which effectively solve misoperation problems of such type of switch in the project practice process.
作者 欧世锋 李克文 陈千懿 况成忠 陈薇冰 OU Shifeng;LI Kewen;CHEN Qianyi;KUANG Chengzhong;CHEN Weibing(Electric Power Research Institute of Guangxi Power Grid Co., Ltd., Guangxi Nanning 530023, China;Nanning Power Supply Bureau, Guangxi Power Grid Co., Ltd., Guangxi Nanning 530023, China)
出处 《广西电力》 2019年第1期41-44,共4页 Guangxi Electric Power
基金 广西电网有限责任公司科技项目(GXKJXM20160236)
关键词 自动化开关 误动作 控制器电源 仿真分析 automatic switch misoperation controller power simulation analysis
  • 相关文献

参考文献1

二级参考文献3

共引文献87

同被引文献6

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部