对重庆110 kV高家坪变电站110 kV母线电容式电压互感器(CVT)红外测温异常原因进行分析,确定了导致该CVT红外测温异常的原因,并针对该问题采取相应的处理方案加以解决,同时明确了电容式电压互感器日常检修维护中的注意事项。
This paper introduces the anomaly analysis of the infrared temperature measurement of the 110 kV bus capacitor voltage transformer of the 110 kV Gaojiaping transformer substation in Chongqing.In addition,it expounds the causes as well as giving relevant solution.Finally,it clarifies the points for attention in daily overhauling and maintenance of the CVT.