某220kV变压器短路损坏的原因分析

Analysis of Short Circuit Damage of a 220kV Transformer
下载PDF
导出
摘要 介绍了一起近区短路引起220kV变压器损坏的事故。事故中,C相低压绕组在3个导线换位处(S弯)发生了短路、断股,分析认为绕组工艺问题、楔形垫块松动、未考虑S弯处自粘换位导线在高温下的粘合强度是主要原因,并对事故后变比试验的错误数据进行了说明。通过查阅文献,发现曾发生若干起类似事故,建议该共性问题引起重视。 An accident involving a 220 kV transformer damage caused by short circuit in the near area was analyzed.After accidents,it is found that three cases of short-circuit and strand breakage occurred at where wires transposed at C-phase low-voltage windings.Analysis led to the conclusion that the winding process problem,loose wedge-shaped block,and less consideration on the adhesive strength of self-adhesive transposed wires under high-temperature are the main reasons for the accident.Erroneous data of the post-accident ratio test was expounded.By consulting the literature,it is found that several similar accidents have ever happened and it is suggested that the common problems should be aroused attention.
作者 滑勉 卢洪宝 李新星 HUA Mian;LU Hongbao;LI Xinxing(State Shanxi Electric Power Corporation,Taiyuan,Shanxi 030001,China)
出处 《山西电力》 2019年第1期14-18,共5页 Shanxi Electric Power
关键词 变压器 换位导线 粘合强度 变比试验 transformer transposed conductor adhesive strength ratio test