摘要
对绝缘油老化引起的一起变压器重瓦斯误动作故障进行了分析,对可能造成重瓦斯动作的原因进行了试验,最终确认重瓦斯动作为瓦斯继电器内部受潮短路所致,并根据故障情况提出了相应的解决办法和建议。
This paper analyzed the heavy gas misoperation of the transformer caused by the aging of the insulating oil. The possible causes of heavy gas action were tested. Finally,it is confirmed that the heavy gas action is caused by the short circuit inside the gas relay due to the damp. According to the fault situation,the corresponding solutions and suggestions are put forward.
作者
赵铁羽
周君杰
朱婷
杨富淇
ZHAO Tieyu;ZHOU Junjie;ZHU Ting;YANG Fuqi(Bishan Power Supply Branch of State Grid Chongqing Electric Power Corporation,Chongqing 402760,China;Maintenance Branch Company of State Grid Chongqing Electric Power Corporation,Chongqing 400000,China)
出处
《电工技术》
2019年第5期64-65,共2页
Electric Engineering