摘要
针对某500kV输电线路距离手合加速跳闸事故,分析事故原因为线路压变端子箱内为第二套线路保护提供测量电压的空开存在质量问题,导致第二套线路保护测量阻抗几乎为零,距离手合加速出口动作跳开开关,最后提出整改建议,以防此类事故的再次发生。
To the accident of distance hand-acceleration trip in 500kV transmission line,it was analyzed that there was a problem with the air switch which provided measuring voltage for the second line protection in the PT box. As a result,the measuring impedance of the second line protection was almost zero after the circuit breaker was closed. The protection action of distance hand-acceleration led to the opening of the circuit breaker. In order to prevent such trip accidents from happening again the rectified suggestions were proposed.
作者
段明明
DUAN Mingming(Maintenance Company Changzhou Branch,State Grid Jiangsu Electric Power Co.,Ltd.,Changzhou 213000,China)
出处
《电工技术》
2019年第5期82-83,85,共3页
Electric Engineering
关键词
距离手合加速
空开质量
测量阻抗
distance hand-acceleration
air switch quality
measuring impedance