摘要
单一方法难以准确判断配网中干式电压互感器故障原因。基于状态检测技术对故障及同批次同型号正常的电压互感器进行停电、带电检测与运行状态仿真,综合分析其绝缘与电气性能,准确判断出故障原因,从而有针对性地提出制造工艺或系统运行方式的改进等预控措施。通过对10 kV干式电压互感器故障分析实例,验证了采用状态检测技术诊断干式电压互感器的有效性及必要性。
It is difficult to use a single method to make an accurate judgment about fault causes of the dry potential transformer in the distribution network. Based on status test technology, power-off test, live test and simulation of operational state were carried out on the faults as well as normal potential transformers of the same type and same batch, a comprehensive analysis of their insulation and electrical performance was made, and fault causes were determined accurately, so that specific precaution measures might be proposed with regards to improvement of manufacturing process or system operation mode. The effectiveness and necessity of adoption of status test technology for the diagnosis of the dry potential transformer was verified in a fault analysis case of a 10 kV dry potential transformer.
作者
伍弘
张利花
马飞越
魏亮
牛勃
Wu Hong;Zhang Lihua;Ma Feiyue;Wei Liang;Niu Bo(Electric Power Research Institute, State Grid Ningxia Electric Power Co., Ltd.,Yinchuan Ningxia 750011, China;Maintenance Co., State Grid Ningxia Electric Power Co., Ltd., Yinchuan Ningxia 750022, China)
出处
《电气自动化》
2019年第2期108-112,共5页
Electrical Automation
关键词
电压互感器
配电网
状态检测
高频局放
励磁特性
故障诊断
potential transformer
power distribution network
status test
high frequency partial discharge
excitation characteristic
fault diagnosis