摘要
以重庆居住建筑典型户型为例,采用EnergyPlus软件对既有居住建筑的供暖、供冷负荷及能耗进行了模拟,分析了使用不同被动技术改造组合时供暖、供冷负荷情况。基于20 kW·h/m^2的供暖、供冷总能耗目标,计算了不同被动技术改造组合下的最低全年性能系数,作为主动性能提升的参考。提出了集成式建筑被动技术改造优化与主动性能提升相结合的低能耗设计策略,可为位于长江流域的重庆地区既有居住建筑节能设计与高效运行提供路径和方法。
Taking a typical urban residential building in Chongqing as an example,analyses the heating and cooling loads and energy consumption of existing residential buildings using EnergyPlus software.Investigates the heating and cooling loads using different passive measure combinations.Aiming at 20 kWh/m^2 of the annual total space heating and cooling energy consumption target,calculates the lowest annual performance factor under different passive technology design combinations as a reference for active system performance improvement.Proposes a low energy consumption retrofit strategy combining passive technology optimization and active performance improvement,which provides a pathway and a method for energy efficient building design and system operation of existing residential buildings in Chongqing of the Yangtze River Basin.
作者
李信仪
王晗
喻伟
刘猛
姚润明
Li Xinyi;Wang Han;Yu Wei;Liu Meng;Yao Runming(Chongqing University,Chongqing,China)
出处
《暖通空调》
2019年第4期49-55,132,共8页
Heating Ventilating & Air Conditioning
基金
"十三五"国家重点研发计划项目"长江流域建筑供暖空调解决方案和相应系统"(编号:2016YFC0700301)
国家自然科学基金国际(地区)合作与交流项目"基于气候响应和建筑耦合的低碳城市供暖供冷方法与机理研究"(编号:51561135002
EP/N009797/1)
关键词
长江流域
既有居住建筑
被动技术改造
主动性能提升
集成优化
Yangtze River Basin
existing residential building
passive technology transformation
active performance improvement
integrated optimization