铝电解整流机组非典型误动跳闸分析及技改探讨 被引量:1

Analysis of atypical malfunction tripping of rectifier unit and discussion on technical reform
下载PDF
导出
摘要 整流机组是电解铝企业生产重要的大型供电设备,一旦发生供电中断,将对企业生产造成重大经济损失。某国有大型企业220kV开关站在进行正常倒闸操作过程中,拉开/合上220kV母线侧隔离开关时,多次导致单台整流机组误动跳闸,对整流机组系统的平稳运行形成极大的安全隐患。本文针对该非典型重大缺陷问题,专业人员对图纸、故障信息、现场等情况进行分析、专家会诊,经技术改造,有效排除了整流机组非典型误动跳闸的故障。 Rectifier units are important large-scale power supply equipments for electrolytic aluminum enterprises. Once power interruption occurs, they will cause significant economic losses to the company's production. When a 220kV switchgear station of a large state-owned enterprise was performing a normal switching operation, when the 220kV busbar side switch was opened/closed, it repeatedly caused a single rectifier to trip by mistake, which caused great problems in the smooth operation of the rectifier system. Potential safety hazards. For this atypical and major defect problem, professionals analyze the drawings, fault information, on-site situations, and expert consultations, and after technical transformation, effectively solve the tripping failure of the rectifier unit's atypical malfunction.
作者 李落印 Li Luoyin(Qineng Electricity-Aluminum of Chongqing Energy,Chongqing 401420)
出处 《电气技术》 2019年第5期74-78,95,共6页 Electrical Engineering
关键词 整流机组 非典型误动跳闸 分析 技术改造 rectifier unit atypical false trip analysis technical transformation
  • 相关文献

参考文献4

二级参考文献27

  • 1唐文前.控制电缆屏蔽层接地方式探讨[J].电力建设,2002,23(7):40-41. 被引量:6
  • 2侯俊,王建国,饶章权,余军,周文俊,胡瑜.500kV隔离开关操作时电流互感器二次侧干扰信号的测试与分析[J].电测与仪表,2005,42(6):41-43. 被引量:9
  • 3Fujimoto N.Mechanism and analysis of short raise-time GIS transients[C]//CIGRE Symposium,Vienna,Aastria,1987:5-7.
  • 4Fujimoto N,Dick E P,Bosggs S A,et al.Transient ground potential rises in Gas insulated substations-experimental studies[J].IEEE Transactions on Power Apparatusand System,1982,101(11):3603-3609.
  • 5Dick E P,Fujimoto N,Ford G L,et a1.Transient ground potential rises in gas insulated substations-problem identification and mitigation[J].IEEE Transactions on Power Apparatus and System,1982,101(11):3610-3619.
  • 6Haznadar Z,Carsimamovic S,Mahmutcehajic R.More accurate modeling of gas insulated substation components in digital simulations of very fast electromagnetic transients[J].IEEE Transactions on Power Delivery,1992,7(1):434-441.
  • 7Nitzschke D,Bauer H.Simulation of transient disturbance voltages in substations using a combination of MoM and TLT[C]//EMC Zurich 2001 Symposium,Zurich,Switzerland,2001.
  • 8Gustavsen B,Semlyen A.Rational approximation of frequency domain Responses by vector fitting[J].IEEE Transactions on Power Delivery,1999,l4(7):1052-1061.
  • 9Heimbach M.VFT studies on current and voltage transformersin GIS by means of all iterative pole-zero-removal method for simulating the transfer function[C]//9th International Graz,Symposium on High Voltage Engineering,Graz,Austria,1995.
  • 10Zhang Zhongyuan,Liang Guishu,Cui Xiang,et a1.A high frequency transfer function model of potential transformer in GIS[C]//2002 3rd International Symposium on Electromagnetic Compatibility,Beijing,2002.

共引文献85

同被引文献1

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部