摘要 为了提高隔爆馈电开关的稳定性和安全性,从真空灭弧室触头和材料选择等方面对隔爆馈电开关结构进行优化,具体实施方案为:将隔爆馈电开关的真空灭弧室触头改为折线形横磁触头;触头材料选用铜铬合金;真空灭弧室内的动导电杆和进线排之间加入"U"型软连接的补偿措施。结果表明:改进后的隔爆馈电开关短路分断电流增加,短延时开断能力提高。 In order to improve the stability and safety of explosion-proof feeder switch,the structure of the flameproof feeder switch is optimized from the contact and material selection of the vacuum interrupter.The concrete implementation scheme is as follows: the contact of the vacuum interrupter of the flameproof feeder switch is changed into a special-shape transverse magnetic contact;the contact material is copper-chromium alloy.The U “soft link” compensation measure is added between the moving guide pole and the incoming line in the vacuum interrupter chamber.The results show that the improved flameproof feeder switch is satisfied.
作者 殷艳哲 YIN Yan-zhe(Xishan Coal and Electricity Group Tunlan Mine,Taiyuan 030200,China)
机构地区 西山煤电屯兰矿
出处 《机械工程与自动化》 2019年第3期217-218,共2页 Mechanical Engineering & Automation