摘要
交流滤波器是直流输电系统中用于滤除谐波和补偿无功的重要设备,一旦发生故障,将影响直流系统的稳定运行。交流滤波器差动保护作为滤波器主保护之一,是滤波器安全稳定运行的前提之一。本文通过对一起由于滤波器光CT合并单元故障导致差动保护动作的实例进行分析,介绍了差动保护的动作原理和存在的问题,并提出相应的防范措施。
The AC filter is an important device in the DC transmission system for filtering harmonics and compensating for reactive power. Once a fault occurs, it will affect the stable operation of the DC system. AC filter differential protection is one of the main protections of the filter and one of the prerequisites for safe and stable operation of the filter. This paper introduces an example of the differential protection action caused by the failure of the filter optical CT merging unit, introduces the action principle and existing problems of the differential protection, and proposes corresponding preventive measures.
作者
杨江涛
郑映斌
刘会鹏
田小龙
叶天舒
YANG Jiangtao;ZHENG Yingbin;LIU Huipeng;TIAN Xiaolong;YE Tianshu(State Grid Hunan Electrical Power Company Limited Maintenance Company, Changsha 410004, China)
出处
《湖南电力》
2019年第2期57-60,64,共5页
Hunan Electric Power
关键词
直流输电系统
交流滤波器
差动保护
合并单元
防范措施
DC transmission system
AC filter
differential protection
combination unit of light CT
preventive measures