主变套管零序TA接线故障分析

Fault Analysis of Zero-Sequence TA Wiring for Main Transformer Bushing
下载PDF
导出
摘要 分析了某地区一起110 kV线路故障导致主变高压侧间隙过流保护动作三侧开关跳闸的事故。通过调阅主变高、中压侧故障录波波形以及对系统零序网络分析,发现主变高、中压侧零序套管TA接反导致线路接地故障,主变高压侧间隙过流保护感受到零序电流从而越级动作,并针对该起事故暴露出的问题,提出了具有针对性的整改措施和建议。 This paper analyses a tripping accident of three-side switch caused by a 110 kV line fault in a certain area,which resulted in clearance overcurrent protection action of the high voltage side of the main transformer.Through reading the fault recording waveforms of the high and medium voltage side of the main transformer and analyzing the zero sequence network of the system,it is found that the TA reversed wiring of the zero sequence casing on the high and medium voltage side of the main transformer led to the grounding fault of the line,which makes the gap overcurrent protection of the high voltage side of the main transformer feel the zero sequence current and thus overstep the operation,and puts forward the targeted rectification measures and suggestions in view of the problems exposed in the accident.
作者 吴培涛 WU Peitao(State Grid Ningxia Electric Power Co.,Ltd.Training Center,Yinchuan 750002,China)
出处 《国网技术学院学报》 2019年第2期17-19,共3页 Journal of State Grid Technology College
关键词 保护越级 零序TA 间隙过流保护 故障录波 零序网络 protection overstep zero-sequence TA gap over-current protection fault record zero-sequence network
  • 相关文献

参考文献3

二级参考文献5

  • 1国家电力调度通信中心.电力系统继电保护实用技术问答[M].北京:中国电力出版社,2004
  • 2贺家李,宋从矩.电力系统继电保护原理[M].北京:中国电力出版社,2007.
  • 3Q/GDW267-2009,继电保护和电网安全自动装置现场工作保安规定[S].
  • 4谢宝炎,王大从,蒙定中,李文毅.继电保护及电网安全自动装置检验条例[M].北京:水利电力出版社,1998.
  • 5李磊.一起因寄生回路引起控制回路异常的情况分析[J].电子世界,2014(5):186-186. 被引量:1

共引文献6

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部